Treatment Cooling Tower and Chiller
WATER TREATMENT COOLING SYSTEM
Daily and Weekly Treatment
- Stand by technicians on site every day.
- Check the condition and daily water analysis of feed & basin.
- Pouring CHAM Clean Chemical.
- Cleaning Basin, Filler and Nozzle.
- Monitoring Approach Chiller every week.
Daily Water Analysis Report
Monthly Treatment
- Feed water analysis, cooling tower, chiller water and its report.
- Recording & sending Chemical Treatment Usage Report.
- Making & sending Minutes every month
Three and Six Monthly Treatment
- Checking the strainer and General Cleaning Strainer WCP every three months.
- Washing the Chiller if the condenser approach is more than 3 Celsius with a brushing machine or chemical.
- Conducting Water Analysis by an Independent Agency every six months
Monthly Water Analysis Report
Example of Cleaning Cooling Tower Report Contents
Chiller Cleaning Report Content Example
Example of PAC Cleaning Report Contents
Note: *Job Report is sent every time cleaning is completed
Cooling Tower Treatment
1. Spray | 2. Tub Brush | 3. Cooling Grid Brush |
![]() |
![]() |
![]() |
4. Vacuum Basin Cooling Tower | 5. Ground Makeup Water Tank Brush | 6. Spray Ground Make up water Tank |
![]() |
![]() |
![]() |
Chemical for Cooling Tower Water
CHAM Clean 050 - Corrosion Inhibitors and Scale Inhibitors
![]() |
CC 050 controls the formation of scale, rust and deposits in open recirculation cooling systems (cooling towers). CHAM Clean 050 Advantages:
|
CHAM Clean 051 - Mikroorganism Control
![]() |
CC 051 prevents duplication, stops cellular processes and metabolic reactions or destroys cell walls.CHAM Clean 051 Advantages:
|
CHAM Clean 051B - Non Oxidizing Biocide
![]() |
CC 051B controls corrosion, deposits and foulants. The Corrosion Inhibitor content in it is very effective in preventing corrosion by forming a protective layer on the metal surface. |
Chiller Cleaning
1. Closing the in & out valves | 2. Lower the Cover | 3. Borescope photo before cleaning | 4. Pour in the chemical |
![]() |
![]() |
![]() |
![]() |
5. Brushing Tube by Tube | 6. Spray tube condenser & cover | 7. Borescope photo after cleaning | 8. Close the in & out valves |
![]() |
![]() |
![]() |
![]() |
**Before & After Chiller Cleaning
Chemical for Chilled Water
CHAM Clean 045 – Closed Circuit Corrosion Inhibitor
![]() |
CC 045 controls corrosion, deposits and foulants. The Corrosion Inhibitor content in CC 045 is very effective in preventing corrosion by forming a protective layer on the metal surface. |